Deck-mounted single control mechanical mixers /
Mixer H. 95mm
Mechanical mixer with pressure-balancing or ceramic cartridge, smooth interior
MIXERS & TAPS FOR WASHBASINS
• Spout H. 95mm L. 120mm with BIOSAFE hygienic outlet.
• Spout suitable for fitting a BIOFIL point-of-use filter (see page 23).
• Ø 35mm standard ceramic or pressure-balancing cartridge.
• Pre-set maximum temperature limiter.
• Body and spout with smooth interiors and low water volume (reduces
bacterial development).
• Tested without water to comply with NHS requirements (UK). Hygiene lever
• Thermal shocks are easy to undertake without removing the control lever
or shutting off the cold water supply (see page 13).
• Flow rate regulated at 5 lpm.
• Fixing reinforced by 2 stainless steel rods.
• Suitable for people with reduced mobility.
• 30-year warranty.
On EP pressure-balancing versions:
• Anti-scalding safety: HW flow rate is reduced if CW supply fails.
• Stable temperature regardless of pressure and flow rate variations.
• Flow rate limited to 5 lpm at 3 bar.
• Filters and non-return valves.
Copper tails
PEX flexibles Ø15mm for
F⅜" comp. fittings
(UK/Ireland)
Mechanical mixer H. 95mm L. 120mm
With pressure-balancing 120 95
Solid lever, with pop-up waste 1¼" in stainless steel 2720TEP -
Solid lever, without waste 2721TEP -
Hygiene lever L. 150mm, with pop-up waste 1¼" 50 max
in stainless steel 2720LEP -
Hygiene lever L. 150mm, without waste 2721LEP 27216LEP 400
With standard ceramic cartridge
Solid lever, with pop-up waste 1¼" in stainless steel 2720T -
Solid lever, without waste 2721T -
Hygiene lever L. 150mm, with pop-up waste 1¼" 2720L - 3/8"
in stainless steel
Hygiene lever L. 150mm, without waste 2721L 27216L
Options: wastes for models without pop-up wastes (see page 99),
BIOFIL tap filters (see page 23)
2721T
Mixers & taps for washbasins 43